Automatic Burner Control Unit

Automatic Burner Control Unit
Automatic Burner Control Unit
Price And Quantity
  • Unit/Units
  • 1
  • Unit/Units
  • 1 INR
    Product Specifications
    • burner controllers
    • Standard
    • -40 to +80 Celsius (oC)
    • Standard
    • Standard
    • 610 Grams (g)
    • 1 Year
    Product Description
    Features:
    • For directly ignited burners of unlimited capacity in continuous operation pursuant to EN 746-2
    • Continuous self-testing for faults
    • Immediate fault lock-out or restart following flame failure available as a switchable function
    • Flame control with UV sensor or ionization sensor
    • Diverse installation possibilities via holes or snap mechanism for DIN rail
    • Space-saving installation on site with IFD 258..I with integrated ignition
    • Display for program status and flame signal intensity
    Application:
    • Automatic burner control unit IFD 258 ignites and monitors directly ignited industrial gas burners of unlimited capacity.
    • As a result of its fully electronic design it reacts quickly to various process requirements and is therefore also suitable for frequent cycling operation.
    • It can be used for atmospheric burners or forced draught burners in multiple burner applications
    • Where a central control system is used for pre-purge and for monitoring.
    • The burners may be modulating or stagecontrolled.
    • The automatic burner control is suitable for operation in grounded and ungrounded systems.
    • The program status and the level of the flame signal can be read directly from the unit.
    • The switch-off threshold can be set using a potentiometer.
    • The behaviour in the event of flame failure during operation can be selected using a switch.
    • Either an immediate fault lock-out or a restart occurs.
    Forced Draught Burners:
    • Control: On/Off
    • Gas valve and air valve are activated simultaneously.
    • The burner is ignited and monitored by a single electrode.
    • In the event of a flame failure, an immediate fault lock-out occurs.
    Two-stage Controlled Burner:
    • Control: On/Off or On/High/Low/Off
    • The burner BIO/BIC starts at low-fire rate.
    • Once the normal operating state is reached
    • The automatic burner control unit for continuous
    • Operation IFD 258 will release control.
    • The PLC can now pulse the air solenoid valve
    • VRR in order to control the capacity between high and low fire.
    Modulating Controlled Burner:
    • Control: On/Off/continuous
    • The PLC uses the actuator IC 20 to move the air butterfly valve BVA to ignition position.
    • The burner BIO/BIC starts at low-fire rate.
    • Once the normal operating state is reached
    • The PLC uses the actuator IC 20 and the air butterfly valve BVA to control the burner capacity.
    Mains voltage for grounded and ungrounded mains:
    • 200 V AC, -15/+10%, 50/60 Hz
    • 120 V AC, -15/+10%, 50/60 Hz
    • 100 V AC, -15/+10%, 50/60 Hz
    • 230 V AC, -15/+10%, 50/60 Hz

     